EOL resistor and Line monitoring using EOLR ? (end of line resistors).what are these terms?

EOLR Or End of line resistors .What are they?  A specially made resistor???

They are ordinary resistors .As the name implies, they are connected at the end of the line…..!!!!

End of line resistors are resistors connected at the end of a signal loop . In  Control systems  and signal circuit,supervision of a loop can be done by the proper connection  of resistors at the device end .By supervision of the loop means  whether the loop is faulty or not . which means any wire break or short circuit ,ground fault etc in the loop. They make false alarms or false status .In control systems like security systems and fire alarm systems a false alarm is critical  and may cause huge loss.So detecting the line fault in addition to the conventional device status is required .In simple terms we call this technique as Line Monitoring .The  design of such systems should be done properly .

While establishing the  wiring  and circuit of such systems  EOLR ( End of line resistors)  plays as a important component of each signal loop .Or each zone etc .Let us examine how the circuit works .

Ordinary signal loop -(No EOLR )

 

Let us take an example of an ordinary signal loop . A device which gives a discrete status is connected to a control room panel . No EOLR employed in this loop .The device is meant to give normal and activated or alarm status .(A pressure switch,a smoke detector, fire detector , level switch etc  .) A close condition will regarded as normal state and open contact as alarm state .see below figure .

 

Device contact Close( max current) ——– normal 

Device contact open (min /no current)——- Alarm

 

So That is the case .A receiving or detecting circuit checks the loop continuously .They receives either a maximum current  or no current And they reports it as normal or alarm condition respectively .

What is  the problem in this type of detection????

In the above case we can only gets two status of the field device.Device in normal condition or in alarm condition .What if the loop wire got shorted or got open?

See the diagram .

 

In the above image ,see case3&4 .So in addition to the normal and alarm condition( case 1&2) ,there are two faulty  status of the signal loop . For wire break and wire short.

So the four conditions of the loop are

Normal 

Alarm

Loop short

Loop open.

How an ordinary monitoring system respond to the above four cases .By ordinary it means the input card or monitoring devices is not designed to report line faults .You can see the system see  similar status in wire break and wire short conditions .

Means it detects same loop current , when,

1 .Device in normal status  and

2 .wire short .

And it detects same loop current when 

1.Device in alarm status

               and 

2.wire break see below table

 

 

The loop current values (or loop resistance) are same in normal and wire short conditions .Also it is same in alarm and wire break conditions .So the system detects same current levels  in different field conditions .Means the whole system doesn’t  distinguish these different conditions .A monitoring card or control room input device reports same statuses at different conditions .see below diagram .The system only reports normal and alarm status .The loop or line is not monitored in this type of design

 .see case 3 & 4

The input detecting card reports the status as normal in wire short conditions !!!!!!!

Also it reports alarm in wire break conditions?!! 

No Line monitoring using EOLR ordinary loop

why ordinary monitoring systems reports false status?

What we learned From the above examples ???

Why detecting circuit  or input channel failed to detects these line faults (case 3&4)

We already learned 

 Two reasons

 1. The monitoring device  is designed or programmed to report these two conditions only .normal and alarm.(contact close or open)

2 .Another reason is  similar current or field resistance values are fed to the  detecting circuit in different field conditions . 

The similar conditions are

1.Close contact  and wires short 

This conditions gives maximum current in the loop .Means a contact short results maximum current in the loop .Also loop wires short gives the same result .So these close contact  and shorted loop are not distinguishable in such circuits .

2 .An open contact and wire break

This  causes no current in the loop .And these open contact and wire break  are not distinguishable in such circuits .

How to detect line faults?

So how to detect line faults in addition to ordinary normal and alarm status of the device.

1.Design and program a detecting circuit which detects these field status.

Normal

Alarm

Loop short

Wire break 

So detecting circuit should be designed and programmed accordingly .It should detect the above  four conditions .Means it should programmed or configured  to detect these four conditions .

2.Arrange field circuit to give these four current levels .Means input card should receive different current values at different conditions .So it could easily distinguish these conditions.

But how?

Here it is …..use EOLR

End of line  resistors.

Line monitoring using EOLR

 A properly arranged resistors at the device end and a properly programmed i/o input card or module or detecting circuit will eliminate false alarms .And  monitoring of the line can be done effectively .The value of resistors  may depends upon the input channel  current range limits .

 

Line monitoring using EOLR - Resistance values

See the above diagram .A field device is fitted with end of line resistors .One is in series and one in parallel with the loop .Both are connected at the end of the signal loop hence the name end of line resistors .Supervision of the loop can be done effectively with this arrangement .

See the four cases below . The four conditions are shown .And in four conditions we get the different field resistances . Accordingly we will get the four distinguishable levels  of loop current .So these four current levels can be programmed as four status .See the below figure .End of line resistors are connected at the field end of the loop .Four conditions are shown . Field resistance values seen from the monitoring card or device is shown .

 

Line monitoring using EOLR - Resistance values

Let’s see the circuit conditions in these four cases. Means what are the values of loop current and field resistances .See figure below .You can see the system receives different loop current corresponding to the four field conditions.This is because of the arrangement of resistors at the device end .

See below table .

 

Line monitoring using EOLR

Line monitoring using EOLR - Resistance values and loop current

So the system detects different current levels  in different field conditions .Means it has  capability to distinguish these different conditions .It reports the line faults in addition to the conventional normal and alarm status . .Means the  loop or line is monitored .See figure below.

..

Line monitoring using EOLR

See figure above .The four field conditions are fed to the input card by four different current levels  .And the input card distinguishes  these conditions

Note: This article only describes simple line monitoring methods  and it’s basic concepts . More complex and advanced line monitoring systems and design are available and we will describe it in another article .