I/P converter or current to pressure converter is the device used to  convert the electrical signal in to air pressure . It is  mainly used for the operation of Pneumatically operated  control valves .Most of the industrial applications use electrical type control signals . However final control elements like control valves (pneumatically operated) need air pressure for its actuation .In such situation it is essential to convert the signal in electrical form to corresponding pneumatic signal. And calibration  of i/p converter also need to be done regularly for the correct outcome .

so these electrical signal is converted in to Pneumatic   form in order to operate the pneumatically  operated  control valve .l/p converter  will do this job .

l/P transducer working

See figure above .In I/P  the input  electrical signal is in voltage or current form such as  4-20 milliampere signal . And  output is  in Pressure form.Mostly used standard is  3-15 Psi output.Air pressure of 20 psi needed as a working supply pressure for the I/P .

I/p converter

To know how I/p converter woks see here  I/P transducer working 

calibration

I/P converter calibration 

Calibration of I/P done by sourcing input milliamperes( 4-20mA)from  a standard  master device and  compare the  pneumatic output with a  standard pressure receiving device .An output of 3-15 psi is expected corresponding to the 4-20mA input signal. Adjustments has to done to make the output same with the reference values .

Materials required for calibration of i,/p converter 

I/P converter 

Milliampre source or calibrator

Pressure calibrator or pressure source

 Pressure indicating master device 

     Or

Digital pressure indicator with required accuracy .

Pressure regulator .

Tools required

Adjustable spanner

Screw driver

Calibration set up for l/p converter 

1 .Connect a milliampere source to the input terminals of I/P

2 .Connect a supply pressure of 20 psi to the supply port of I/P. A pressure source with connected pressure regulator can be used for this purpose .Adjust the regulator output to 20psi .

3 .connect output port to a standard   pressure indicating device  through proper tubings and fittings .

calibration of I/p converter

Calibration

Apply 4 mA to the I/P .check output .It should be 3 psi . If not adjust the output to 3 psi using  ‘ZERO’adjusting screw .

2.Apply 20mA . check output .It should be 15 psi.If not adjust the output to 15 psi by’ SPAN ‘adjusting screw.

repeat above steps 1 and 2 untill we are getting precisely 3 and15 psi corresponding to 4 and 20mA respectively .

3.check  for the other points. As given by the below table.

 Input              Output

  4  mA             3  psi

  8  mA             6  psi

12  mA             9  psi

16  mA           12  psi

20  mA           15  psi