pressure switch

what is pressure switch
An electric switch operated by means of pressure is called pressure switch. It makes or breakes the electric contacts at the desired setpoint. They can be used for initiating an alarm or operate a desired function through properly designed circuit or functioning with any other control elements. They can be used for sensing  a ‘pressure  high ‘ condition or  ‘pressure  low ‘ condition with respect to a setpoint.
pressure switch
credits:switzer process instruments pvtltd
example
Compressor control 
an instrument air compressor starts when the header pressure falls below for example 45 psi and stops when it is rise above 60 psi.
 
example
Turbine trips when lube oil pressure falls below setpoint.This is done with the help of pressure switch çonnected in the lube oil line .
how they works
 

The pressure acting on the sensing element is transferred to a mechanical assembly  .And this mechanical assembly is linked to a micro switch .So the applied pressure causes make or break its contacts at some desired setpoint thereby allowing the control circuit open or closed .And the desired operation can be obtained through the control circuit .

where it is used
Discrete control of pressure, like instrument air compressor control,for generating pressure high and low Alarms,In emergency  shutdown, at a specific pressure setpoint  etc .  
 

components

 

1.Setpoint adjusting nut

We can adjust setpoint by increasing or decreasing  the tension on this range adjusting spring .Or setpoint adjusting spring.The movement of mechanical links is the net result of  this tension on the spring  and the force on the bellows  due  to the pressure acting .So we can adjust the setpoint by changing this   spring tension   through  its knob  

2 .Dead band adjusting nut

Dead band of the pressure switch can be adjusted  by changing the tension of another spring .The dead band is the difference in value of pressure between setpoint and reset point .The mechanical links in the pressure switch is so constructed such that once it change its status on applying a specific value of pressure ,it  doesn’t regains  it’s previous status  at the same point on reversal of the pressure signal . It allows a specific band of pressure through which it stays at the new status .Only after that the pressure switch returns to previous status .This is done by properly constructed linkages and spring.The spring tension can be adjusted to get  the required dead band .

3.Microswitch

It is a small switch assembly which operates by means of mechanical movement caused by the pressure . The micro switch  is properly linked to the mechanical assembly.It   consists electric contacts which makes or breaks at the setpoint  and reset points accordingly .

4.electrical connection

Cable entry will be provided  the pressure switch inorder to make electrical connections .one can make connections in the provided NO,NC,COMMON contacts through proper connecting terminals . 

5 Dead band adjusting spring .

6 .Pressure connection

7 .Sensing element

The pressure is fed in to the sensing elements which in turn cause itself to make a  mechanical movement proportional to the applied pressure .Bellows, Diaphragm, bourdon , etc  are the common  sensing  elements used .The pressure applied to these elements cause it to expand  transferr this movement to the links in the pressure switch 

8 Setpoint. adjusting spring

9 .Connection terminals

pressure switch internal parts
 

10 .scale-Dead band

11 .cable entry

12. scale-setpoint

Terminal connection

The output of the pressure switch is a set of contacts which can be used for the desired control action .This contact outputs are connected to terminal connectors .

Scales for setpoint and Dead band

Scales may be provided to indicate setpoint and dead band .one can roughly calibrate a pressure switch by adjusting the setpoint and dead band with the help of this scale .But it is recommended to do the calibration by proper method.ie By applying pressure and adjusting the range and dead band to correct value .

Related terms

Adjustable range
The span of pressure in which setpoint  can be selected and adjusted to a specific point in order to achieve desired control action.
 
Set point 
The value of pressure at which the switch is adjusted so that it change its status on rising or falling pressure is the set point .The contact status changes at this pressure. NO contacts changes in to Close  and NC contact status  changes in to open .
 
For example
PSH (pressure switch High)
Here the pressure switch is so calibrated that it will change its contact at setpoint on increasing pressure .
Ex: A pressure switch PSH set for 7 kg/cm². Here the pressure switch changes its contact status at 7 kg/cm² on rising pressure .
 
 PSL (pressure switch Low) 
Here the pressure switch is so calibrated that it will change its contact at 5 kg/cm² on  falling pressure. .A pressure switch set for PSL 7 Kg/cm² means ,the switch changes its contact status  at 7 kg/cm² on falling pressure 
 
 reset point
The value of pressure at which the pressure switch resets.
 
For’ pressure switch high ‘ reset point has a value below the  setpoint.
 

For’ pressure switch low’ reset point has a value above setpoint

 
Dead band
It is the gap between setpoint and reset point.It is also called hysteresis

PSH and PSL

Pressure switch can be calibrated to sense a pressure high condition or pressure low condition.

PSH

Suppose we want to activate an alarm  or  make a control action when pressure exceeds some predetermined  value.This is achieved by calibrating a pressure switch for a pressure high condition Or PSH.

For example   valve closes when pressure in pipeline exceeds  the limit.

The below figure shows the variation of contact status of a pressure switch  which is calibrated  for Pressure high condition. Pressure is given to pressure switch from zero and increased  and then decreased further.

We can see that pressure switch sets at 60Psi which is the set point which  can be adjusted to a required value through the provision like knob or screw  provided in the pressure switch.After pressure switch sets we decreased the pressure.Then what happens ? Does the pressure switch resets at the same pressure at which it sets??? No…The pressure switch resets at some other points below the setpoint. Called reset point. On examining the curve we can see that pressure switch sets at  60 on increasing pressure and after that on decreasing pressure it resets at 50 psi . The difference in gap between set point and reset point is the dead band of pressure switch .In this case 60 psi is the set point and 50 psi is the reset point and 10 psi ,the dead band .

PSL- pressure switch low

Suppose we want to activate an alarm  or  make a control action when pressure falls below some predetermined  value.This is achieved by calibrating a pressure switch for a pressure low condition Or PSL.

For example   valve closes when pressure in pipeline falls below  a specified value .

The below figure shows the variation of contact status of a pressure switch  which is calibrated  for Pressure low condition.

Pressure is given to pressure switch well above reset point and deceased  and after reaching setpoint pressure is increased  further.

 

On examining the curve we can see that pressure switch sets at  50 psi  on decreasing pressure and after that on increasing pressure it resets at 60 psi . In this case 50 psi is the set point and 60 psi is the reset point and 10 psi ,the dead band.

Calibration

Calibration of pressure switch is make the pressure switch sets and resets at   desired pressure..Pressure switch can be calibrated for sensing a‘pressure low’ condition or ‘pressure high’  condition.Both calibration slightly differs from each other .It is important to note the pressure switch function.ie weather it has to be calibrated for ‘low ‘ condition or for ‘high’ condition .It is important because a pressure switch calibrated to use for   high condition cannot be used for low  condition at the same setpoint .

a pressure switch calibrated for high alarm at a setpoint 60 psi with a dead band of 10 (reset at 50 psi) .It cannot be used as a pressure low switch for the  same setpoint . .If it is to be used as a low switch  the setpoint will be 50 psi  and resetpoint will be at 60 psi.So in order to get a setpoint (for low) of 50 psi it needs to be recalibrated .

Obviously calibration procedure for’ pressure switch low’ and  ‘pressure switch high ‘ is different .Though only a small difference but a critical one .